I = P / (V × PF)DC: I = P / V  ·  three-phase: I = P / (sqrt(3) × V × PF), V line-to-line  ·  S = P / PF

Watts to amps is the step from the power a load uses to the current it draws, I = P / V for direct current. This free watts to amps calculator divides the watts by the supply voltage, and by the power factor and sqrt(3) where alternating current calls for them, so one box covers DC, single-phase and balanced three-phase supplies.

Supply

Single-phase AC: enter the rms supply voltage and the power factor of the load.

Load a real case

Each button chooses the supply type, writes the watts, volts and power factor into the boxes, and puts the tool back on solving for current if you had changed it. The line underneath then quotes the current the calculator itself displays, not a stored answer.

Pick a case above, or type your own numbers.

What Is the Watts to Amps Calculator?

The watts to amps calculator is a free online tool built on I = P / V for direct current, I = P / (V · PF) for single-phase AC and I = P / (sqrt(3) · V · PF) for balanced three-phase AC, where V is the line-to-line voltage. Pick the supply, enter the power, the voltage and the power factor, and it returns the current with the apparent power and every step of the working; switch Solve for to turn amps back into watts or to find the voltage needed.

Variables used by the watts to amps calculator
SymbolQuantityDefault unitAlso acceptsExample value
PPowerWkW1000
VVoltageVkV230
PFPower factor1
ICurrentAmA4.348

How to use the watts to amps calculator

  1. Pick the supply. Press DC, Single-phase AC or Three-phase AC above the boxes. DC hides the power factor box, because the idea has no meaning for a steady current, and three-phase renames the voltage box Line-to-line voltage.
  2. Enter the power. Type the load's power in W or kW, the figure on its rating label. For a motor, enter the electrical input power: the kW on a motor nameplate is the shaft output, and the input is that divided by the efficiency from the data sheet.
  3. Enter the voltage. On single-phase this is the rms supply voltage, such as 230 V (UK/Europe nominal) or 120 V (North America nominal). On three-phase it is the voltage between two lines, such as 400 V or 480 V.
  4. Enter the power factor. Use 1 for a kettle, a heater or a filament lamp, and the nameplate figure for a motor. Anything above 1, or 0 and below, is refused.
  5. Read the result and the extras. The headline is the current. On AC the extras give the Apparent power in VA and the Reactive power in var; Load resistance appears on DC and on single-phase at a power factor of 1, Phase voltage on three-phase, and Power in kW on every supply.
  6. Solve the other way. The Solve for menu turns the tool into an amps to watts converter (Power) or finds the voltage a given power and current imply (Voltage). Open Show working to see the formula for the supply you picked, with your numbers in it.

The headline figure trims trailing zeros, so a 1500 W heater on 120 V shows 12.5 A while the working line, which always carries four significant figures, ends in 12.50 A. They are the same number. The same happens with the headlamp, which shows 5 A in the headline and 5.000 A in the working.

Three slips account for most wrong answers. On three-phase, typing the phase voltage of 230 V instead of the line-to-line 400 V turns the motor preset's 16.98 A into 29.53 A. Leaving the power factor at 1 for a motor under-reads the current, and typing 2000 with kW selected, when watts were meant, asks for 2000 kW and returns 8696 A.

Watts to amps calculator at its default inputs: single-phase AC selected, power 1000 W, voltage 230 V and power factor 1 give a current of 4.348 A, with extras reading apparent power 1000 VA, reactive power 0 var, load resistance 52.90 ohms and power 1.000 kW, and the working I = 1000 / (230 × 1) = 4.348 A.
The page opens on a 1000 W load on 230 V single-phase. The current is 4.348 A, the apparent power equals the real power because the power factor is 1, and the load behaves as a 52.90 Ω resistance.

Worked example: change one thing at a time

Start from the kettle and move as little as possible per row, except at row 7, which jumps to a new load. Every figure in the table is the string the calculator itself displays for those inputs, so if the table and the tool ever disagree, the tool is right. A dash means the calculator shows no such extra for that supply.

What the calculator reports as the supply and the load change
Step Supply Power entered Voltage entered Power factor Current, amps Apparent power Reactive power Load resistance
Start: kettle on UK/EU mains Single-phase 2000 W 230 V 1 8.696 2000 VA 0 var 26.45 Ω
Voltage to 120 V Single-phase 2000 W 120 V 1 16.67 2000 VA 0 var 7.200 Ω
Power to 1500 W Single-phase 1500 W 120 V 1 12.5 1500 VA 0 var 9.600 Ω
Back to 230 V at 1000 W Single-phase 1000 W 230 V 1 4.348 1000 VA 0 var 52.90 Ω
Power factor to 0.8 Single-phase 1000 W 230 V 0.8 5.435 1250 VA 750.0 var
Power to 750 W Single-phase 750 W 230 V 0.8 4.076 937.5 VA 562.5 var
A workshop load at 400 V Single-phase 10 kW 400 V 0.85 29.41 11765 VA 6197 var
Switch to three-phase Three-phase 10 kW 400 V 0.85 16.98 11765 VA 6197 var
Power factor to 1 Three-phase 10 kW 400 V 1 14.43 10000 VA 0 var
Switch to DC: a 12 V headlamp DC 60 W 12 V 5 2.400 Ω

Rows 1 to 3 hold the watts and change the voltage, then the watts. Keeping 2000 W in the power box while the voltage box drops from 230 V to 120 V multiplies the current by 230/120 = 1.917, to 16.67 A, and that describes a second kettle whose element was designed for 120 V. The resistance extra shows it, falling from 26.45 Ω to 7.200 Ω, and the item Two kettles, not one further down gives what the first kettle would really do on 120 V.

Rows 4 to 6 show what the power factor does. At 1000 W and 230 V, lowering it from 1 to 0.8 lifts the current by 1/0.8 = 1.25, from 4.348 A to 5.435 A, while the watts stay put and the apparent power rises to 1250 VA. The resistance extra disappears, because below a power factor of 1 the load is no longer a plain resistor.

Rows 7 to 9 are the motor preset reached one change at a time. Treating 10 kW at 400 V as single-phase gives 29.41 A; pressing Three-phase AC divides that by sqrt(3) = 1.732, to 16.98 A in each line, and the phase voltage extra reads 230.9 V. Raising the power factor to 1 brings it to 14.43 A, smaller by the factor 1/0.85 = 1.176.

Row 10 is the headlamp on DC. The power factor box is hidden, the extras shrink to the load resistance and the power, and 60 W on 12 V comes out at 5 A, ten times the 0.5 A that the same 60 W needs on 120 V.

Formula and symbol reference

The calculator uses three forms of one idea: I = P / V for DC, I = P / (V × PF) for single-phase AC and I = P / (sqrt(3) × V × PF) for balanced three-phase AC. The extras come from S = P / PF, Q = S × sqrt(1 - PF²) and R = V / I, and the reverse modes simply rearrange the same equations, P = V × I × PF and V = P / (I × PF), with sqrt(3) added on three-phase.

Symbols, units and working ranges
Symbol Meaning SI unit Typical range
P Real (active) power of the load, in watts: the electrical input, never a motor's shaft output watt, W 60 W for a car headlamp, 1500 W for a space heater, 2000 W for a kettle, 10 kW for a workshop motor's electrical input.
V The voltage the load is connected to: its rms value on AC, measured between two lines on three-phase volt, V 12 V DC; 120 V (North America nominal) and 230 V (UK/Europe nominal) single-phase; 400 V and 480 V line-to-line three-phase.
I The headline result in amps; on three-phase, what each line carries ampere, A 0.5 A for a 60 W lamp on 120 V, 8.696 A for a kettle on 230 V, 16.98 A per line for the motor taking 10 kW of electrical input.
PF Watts over volt-amperes for the load; hidden and ignored on DC none (a ratio) 1 for heaters, kettles and filament lamps; 0.8 and 0.85 in this page's motor examples. The tool accepts any value above 0 up to 1.
S Apparent power, P / PF: what the supply has to carry volt-ampere, VA Equal to P at a power factor of 1; 937.5 VA for 750 W at 0.8; 11765 VA for 10 kW at 0.85.
Q Reactive power, S × sqrt(1 - PF²): the part that flows back and forth without doing work volt-ampere reactive, var 0 var at a power factor of 1; 562.5 var for 750 W at 0.8; 6197 var for 10 kW at 0.85.
R Load resistance, V / I: shown for DC and for single-phase at a power factor of 1 ohm, Ω 2.400 Ω for the 12 V headlamp, 7.200 Ω for a 2000 W kettle built for 120 V, 26.45 Ω for one built for 230 V.
sqrt(3) The three-phase factor linking line-to-line voltage, phase voltage and line current none 1.732051. Phase voltage = V / sqrt(3), so 400 V line-to-line is 230.9 V line-to-neutral.

The physics: why the supply type changes the current

A volt is a joule per coulomb and an amp is a coulomb per second, so volts times amps is joules per second, which is watts. That is the whole of the DC case, and it is why the calculator refuses to answer without a voltage: the same power can arrive as many coulombs at a low voltage or a few at a high one.

On AC the supply has to carry the Apparent power extra, not just the watts. When voltage and current fall out of step, as they do in a motor, part of the current surges back and forth doing no net work, and the Reactive power extra measures that part, while the number in the power factor box is simply watts over volt-amperes. Dividing by it is what makes the current rise when the power factor falls.

A three-phase supply shares the load between three live conductors whose voltages are staggered evenly through each cycle. The voltage between two lines is sqrt(3) times the voltage from each line to neutral, so the calculator divides by sqrt(3) as well and reports the current in each line, with the line-to-neutral figure as the Phase voltage extra.

Watts to amps calculator loaded with the three-phase motor preset: three-phase AC selected, power 10000 W of electrical input, line-to-line voltage 400 V and power factor 0.85 give a current of 16.98 A per line, with extras reading apparent power 11765 VA, reactive power 6197 var, phase voltage 230.9 V and power 10.00 kW.
The Three-phase motor preset. With the supply set to three-phase the voltage box becomes the line-to-line voltage, and 10 kW of electrical input at 400 V and a power factor of 0.85 draws 16.98 A in each line while the supply carries 11765 VA.

Where the conversion breaks down

The arithmetic is exact. What goes wrong is the number typed into the power box, the power factor assumed for the load, or the supply the formula takes for granted.

A rating is not a measurement
The watts on a label are what the appliance is rated for, and the current the tool returns is the current at that rating. Real draw moves around it: a thermostat switches a heater on and off, and a motor running light takes far less than its full-load figure.
Symptom: a clamp meter reading well below the calculated current on a lightly loaded machine.
A motor's kW is its output
Motor nameplates rate the mechanical power at the shaft, and the motor takes more than that from the supply. What belongs in the power box is the electrical input, shaft kW over efficiency; that efficiency belongs to the particular motor, so take it from its data sheet and verify before use rather than guessing one.
The first moment after switch-on
The result is the current once the load has settled into steady running. For a moment after switch-on, a motor that has not yet spun up or a lamp whose filament is still cold takes far more, and nothing in the boxes can show that surge.
Resistance that changes with temperature
The Load resistance extra is V / I at the rated power, which for a lamp is the hot filament. A multimeter on the cold lamp reads lower, because a metal filament's resistance rises as it heats.
Loads that distort the current
Switch-mode power supplies, chargers and LED drivers draw current in short pulses rather than a smooth sine wave. The formula still holds if the power factor you enter is the true one, which includes that distortion, but a figure that describes only the phase shift under-reads the current.
Unbalanced three-phase
The three-phase formula assumes the same current in all three lines. If the phases are loaded unequally, work each one as a single-phase load on the phase voltage the three-phase extra reports, 230.9 V for a 400 V supply, and expect a different current in each line.
Two kettles, not one
The two kettle presets describe a 2000 W kettle built for each voltage. Plug the 26.45 Ω element of a 230 V kettle into 120 V and, if its resistance stayed constant, it would draw 4.537 A and give only 544.4 W. The watts on a label hold only at the voltage the appliance was built for.

None of this is installation advice. Cable sizes, fuses and circuit breakers are chosen under local wiring regulations, by a qualified electrician, and the current this tool returns is only the starting point of that work.

Where it is actually used

Three-phase workshop machines
Press Single-phase AC with the motor preset loaded and the headline climbs from 16.98 A to 29.41 A, the same 10 kW of electrical input squeezed through one pair of conductors. That factor of sqrt(3) less current per conductor is part of why larger machines are wired for three-phase.
Generators and UPS units rated in VA
The VA figure on a backup supply caps the current it can deliver, and a separate watt figure, where one is given, caps the power. Run each load through the tool, add up the Apparent power extras and compare the total with the VA figure; simple addition errs on the safe side.
12 V battery and solar systems
Low voltage means high current for the same power. The headlamp preset needs 5 A at 12 V, and on DC a 1000 W load would need 83.33 A, which is why low-voltage systems use heavy cables and keep their loads small.
Extension leads and adaptors
A lead or adaptor is rated for a maximum current, and the rating printed on the lead is the figure to compare against. Add the watts of everything plugged into it, enter the total, and set the result beside that printed rating.
Reading a rating label
Most appliances print their watts and their supply voltage, but not their current. For a heater, kettle or other resistive appliance, type the two figures into the boxes with a power factor of 1 and the headline is the current at full power.
Checking a circuit with Ohm's law
On DC, or single-phase at a power factor of 1, the resistance extra gives you the load as a plain resistor, so the result can go straight into an Ohm's law check. The 12 V headlamp behaves as 2.400 Ω, and 12 V across 2.400 Ω gives back the same 5 A.
Watts to amps calculator loaded with the car headlamp preset: DC selected, the power factor box hidden, power 60 W and voltage 12 V give a current of 5 A, with extras reading load resistance 2.400 ohms and power 0.06000 kW, and the working I = 60 / 12 = 5.000 A.
The Car headlamp preset. On DC the power factor box disappears and the working reads I = 60 / 12 = 5.000 A; the headline shows the same current as 5 A, and the lamp's hot filament behaves as a 2.400 Ω resistance.

Where to go next

For the reasoning behind the three formulas, with worked problems that go step by step, read the guide Watts to Amps: Conversion and Formula, and for the relation the resistance extra rests on, the article on Ohm's law. Take the load resistance to the Ohm's law calculator, or the same watts to the electricity cost calculator to see what the load costs to run. Or browse the library of physics simulations.

Frequently asked questions

Why won't the calculator give a current until the voltage box is filled?

Because a wattage on its own fixes only the product of voltage and current, and endless pairs of the two multiply to the same figure. Clear the voltage box and the result area asks for it instead of guessing; type 230 against the default 1000 W and it answers 4.348 A, then type 120 and it answers 8.333 A. Those are two different appliances, each designed around the supply it runs on.

Which formula does the calculator use for DC, single-phase and three-phase?

DC uses I = P / V, and single-phase AC uses I = P / (V × PF), with V the rms supply voltage. With Three-phase AC pressed it switches to I = P / (sqrt(3) × V × PF), reading the voltage box as line-to-line and reporting the current carried by each line. For three-phase, enter the line-to-line figure, such as 400 V or 480 V, not the phase voltage; the tool shows the phase voltage as an extra.

What is power factor and where do I find it?

Power factor is the ratio of real power in watts to apparent power in volt-amperes, a number above 0 and at most 1. It is 1 for resistive loads such as heaters, kettles and filament lamps, and below 1 for motors and other inductive loads, whose nameplates usually state it. If you cannot find it, the current you get with 1 entered is the smallest the load could draw, not the actual figure.

Which figure should I compare with a VA rating?

The Apparent power extra, which the calculator shows on both AC supplies. It matches the watts only while the power factor box holds 1, and grows as that number falls: 750 W at 230 V with a power factor of 0.8 reads 937.5 VA. Many generators and UPS units state a VA figure and a watt figure, so hold the extra against the first and the power you typed against the second.

How do I convert amps to watts?

Change Solve for to Power and enter the current, the voltage and the power factor. On a single-phase supply at a power factor of 1, 13 A at 230 V gives 2990 W and 15 A at 120 V gives 1800 W. On three-phase the tool multiplies by sqrt(3) as well, so 16.98 A at 400 V and a power factor of 0.85 comes back as 9999 W, the rounded current costing one watt.

Why is a motor's nameplate kW not its electrical input power?

A motor rating in kW describes the mechanical power it delivers at the shaft, and some of the energy it takes in is lost as heat inside it. To fill the power box, divide the shaft kW by the efficiency printed on the motor data sheet. Nothing on the page guesses an efficiency, which is why the three-phase preset is labelled as 10 kW of electrical input.

What does the page's default 1000 W case show?

A 1000 W resistive load on 230 V single-phase at a power factor of 1, which the headline turns into 4.348 A. Because nothing is out of step, the apparent power extra matches the 1000 W, the reactive power reads 0 var and the load resistance extra gives 52.90 ohms. Overwrite any box to start your own case, and the working under Show working follows your numbers.

References & formula source

  • Halliday, Resnick & Walker — Fundamentals of Physics, the chapters on current and resistance (power in electric circuits) and on alternating current (power factor).
  • Young & Freedman — University Physics, the chapters "Current, Resistance and Electromotive Force" and "Alternating Current".
  • BIPM — The International System of Units (SI brochure): the definitions of the ampere, the volt and the watt.
  • Further reading: Electric power — Wikipedia

Embed this calculator

Add this free Watts to Amps calculator to your own website — copy the snippet below.